0.66
 
 
 
 
 

0.66

16442-80
60502-1 (1988-11)

 

Application

Cables are designated for electrical power passing and distribution in fixed installations with alternate voltage of frequency 50 Hz in the range of temperatures from 50C below zero till 50C above zero.

 

Construction

Cableleads
Round aluminum and copper, one – wire and multiwire (class 1,2 GOST 22483-77).

Insulation and shell
PVC.

Serving
type according to GOST 7006-72 Armature from steel strips, PVC jacket.

Technical characteristics

Cable mark Cable leads amount Nominal main cable leads cut, mm²
2, 3, 4 4.0 — 50

Cable leads electrical resistance to direct current should be in accordance with GOST 22483.

Insulation electrical resistance counted in 1 km of length and temperature 20C.

Nominal cable lead cut, mm² Electric resistance of insulation, MOhm, not less
1 — 1.5 12
2.5 — 4 10
6 9
10 — 50 7

It doesn't spread combustion during the single laying.

Protractedly admissible heating temperature for cable leads is 70C.

Factory length, not less than 450 m (for main cable leads cuts 1.5 -16 mm²), 300 m (for main cable leads cuts 25-70 mm²), 200 m (for main cable leads cuts 95-240 mm²).

Cable service life is 30 years.

Warranty period is 5 years since its breaking - in, but not later than 12 months since its manufacture.


Construction data on standard agents

Cable leads amount and nominal cut, mm² Nominal external diameter, mm 1 km cable bulk, kg
1×1,5
1×2,5
1×4,0
1×6,0
1×10
1×16
1×25
1×35
1×50
2×1,5
2×2,5
2×4,0 14,53 362
2×6,0 15,57 429
2×10 17,95 574
2×16 21,05 786
2×25 24,43 1059
2×35 27,11 1436
2×50 30,65 1815
3×1,5
3×2,5
3×4,0 15,08 422
3×6,0 16,19 511
3×10 18,75 696
3×16 22,09 979
3×25 26,12 1389
3×35 28,57 1813
3×50 32,38 2341
3×1,5+1×1,5
3×2,5+1×1,5
3×4,0+1×2,5 16,02 475
3×6,0+1×4,0 17,28 584
3×10+1×6,0 19,61 782
3×16+1×10 23,19 1113
3×25+1×16 28,35 1621
3×35+1×16 30,13 2109
3×50+1×25 34,62 2807
4×1,5
4×2,5
4×4,0 16,02 491
4×6,0 17,28 604
4×10 20,14 838
4×16 23,88 1198
4×25 28,35 1719
4×35 31,1 2325
4×50 35,77 3074