22483-74
60502-1 (1998-11)

 

Application

Cables are designated for joining movable devices to the power grid, having bends with radius not less than 8 cable diameters under the admissible heating temperature of cable leads till 70C above zero, under the environment temperature from 40C below zero till 50C above zero.

 

Construction

Cable leads
Round copper multi-wires, stranded (5 class GOST 22483-74).

Insulation and shell
PVC.

Technical characteristics
Cable mark Cable leads quantity Nominal cut, mm²
- 7 — 37
7 — 10
1.0 — 4.0
6.0

Electrical resistance of cable leads, counted in 1km of cable length and temperature 20C, not less:
a) in case of acceptance and supply – 50 MOhm;
b) for the period of service and storage – 0.05 MOhm.

Cable leads electrical resistance to the direct current corresponds to GOST 22483. For the period of service and storage 120% from rate.

Cables carry test alternate voltage of nominal frequency 50 Hz during 5 minutes without water dip:
a) 2.5 kV - in case of acceptance and supply;
b) 1.5 kV – for the period of service and storage.

Cable factory length is not less than 150 m. It is admitted to pass cables with any lengths under the agreement of consumers.

Protractedly admissible heating temperature for cable leads is 70C.

It doesn't spread combustion during the single laying.

The cables are solar radiation resistible.

The cables are grease oils and diesel fuel resistible.

The cables are resistible under the temperature (25± 10)C to the bends +π/2 having nominal stretching force 49 N (5 kilogram-force) — cable nominal external diameter from 10 till 25 mm — 9000 bend cycles.

Cable stretching force should be not more than 19,6 N (2 kilogram-force) to 1 mm² of cable leads 8 diameters.

Warranty period of cables service is 12 months since its breaking –in, but not later than 18 months since its manufacture.

Service period is not less than 4 years.


Admissible current loads
Number of cable leads Admissible current loads A for single cable laying with nominal cut, mm²
1.0 1.5 2.5 4.0 6.0
7 8.3 10.3 13.4 17.5 21.8
10 7.2 8.8 11.7 15.3 19.0
12 6.6 8.2 10.8 14.1
14 6.3 7.6 10.0 13.1
16 5.9 7.2 9.4 12.3
19 5.5 6.7 8.8 11.5
24 4.9 6.2 8.0 10.5
27 4.7 5.8 7.7 10.1
30 4.5 5.5 7.5 9.8
33 4.2 5.3 7.2 9.4
37 3.9 5.0 6.8 8.9
Construction data on standard agents
Cable leads amount and nominal cut, mm² Nominal external diameter, mm 1 km cable bulk, kg Cable leads amount and nominal cut, mm² Nominal external diameter, mm 1 km cable bulk, kg
7×1.0 12.5 233 7×2.5 14.7 379
10×1.0 15.5 323 10×2.5 19.0 557
12×1.0 16.0 360 12×2.5 19.6 629
14×1.0 16.8 403 14×2.5 20.5 708
16×1.0 17.6 447 16×2.5 21.6 789
19×1.0 19.2 537 19×2.5 22.8 907
24×1.0 22.2 667 24×2.5 27.1 1171
27×1.0 22.6 723 27×2.5 27.7 1279
30×1.0 23.4 785 30×2.5 28.6 1395
33×1.0 24.9 883 33×2.5 30.1 1541
37×1.0 25.8 967 37×2.5 31.2 1696
7×1.5 13.1 274 7×4.0 17.2 538
10×1.5 16.3 381 10×4.0 22.3 790
12×1.5 16.7 428 12×4.0 23.0 897
14×1.5 17.6 481 14×4.0 24.8 1049
16×1.5 19.1 562 16×4.0 26.1 1172
19×1.5 20.1 641 19×4.0 27.5 1348
24×1.5 23.3 798 24×4.0 32.5 1718
27×1.5 23.7 869 27×4.0 33.2 1880
30×1.5 25.2 981 30×4.0 34.3 2053
33×1.5 26.1 1061 33×4.0 36.7 2314
37×1.5 27.1 1164 37×4.0 38.0 2548
      7×6.0 20.1 755
      10×6.0 26.0 1101