Application

Cables are designated for electrical power passing and distribution in fixed installations with alternate voltage of frequency 50 Hz in the range of temperatures from 50°C below zero till 50°C above zero.

 

Construction

Cable leads
Round aluminum and copper, one — wire and multiwire (class 1,2 GOST 22483-77). Sector — shaped copper and aluminum, multi-wire.

Insulation and shell
PVC.

Serving
type according to GOST 7006-72. Armature from steel strips, PVC jacket.

Technical characteristics

Cable mark Cable leads amount Nominal main cable leads cut, mm²
Round Sector
2, 3, 4 6,0 — 240
3, 4 70 — 240

Insulation electrical resistance counted in 1 km of length and temperature 20C.

Nominal cable lead cut, mm² Electric resistance of insulation, MOhm, not less
1 — 1.5 12
2.5 — 4 10
6 9
10 — 240 7

Insulation electrical resistance counted in 1 km, measured under protractedly admissible heating temperature of cable leads during the running not less than 0,005 MOhm.

Cable leads electrical resistance to direct current complies with GOST 22483.

Cables carry the alternate voltage of nominal frequency 50 Hz during 10 minutes 3.5 kV.

Protractedly admissible heating temperature for cable leads is 70C.

It doesn't spread combustion during the single laying.

Factory length, not less than 450 m (for main cable leads cuts 1.5-16 mm²), 300 m (for main cable leads cuts 25-70 mm²), 200 m (for main cable leads cuts 95-240 mm²).

Warranty period is 5 years since the cable breaking - in.

Manufacturer guarantees cables compliance with terms of present standard under the keeping conditions of service, storage, joining - up.

Cable service life is 30 years.

Cables can be laid without prior heating under the temperature not less than 15C below zero.

Minimum bend radius during lying is not less 15 external diameters of cable.


Construction data on standard agents

Admissive current loads and admissive short-circuit current

Cable leads nominal cut, mm² Admissive current loads, A Admissive one-second short-circuit current, kA
one-lead cable two-lead cable three-lead cable*
In the air In the ground In the air In the ground In the air In the ground
Cables with copper cable leads
1.5 29 32 24 33 21 28 0.17
2.5 40 42 33 44 28 37 0.27
4 53 54 44 56 37 48 0.43
6 67 67 56 71 49 58 0.65
10 91 89 76 94 66 77 1.09
16 121 116 101 123 87 100 1.74
25 160 148 134 157 115 130 2.78
35 197 178 166 190 141 158 3.86
50 247 217 208 230 177 192 5.23
70 318 265 226 237 7.54
95 386 314 274 280 10.48
120 450 358 321 321 13.21
150 521 406 370 363 16.30
185 594 455 421 406 20.39
240 704 525 499 468 26.80
Cables with aluminum cable leads
2.5 30 32 25 33 21 28 0.18
4 40 41 34 43 29 37 0.29
6 51 52 43 54 37 44 0.42
10 69 68 58 72 50 59 0.70
16 93 83 77 94 67 77 1.13
25 122 113 103 120 88 100 1.81
35 151 136 127 145 109 121 2.50
50 189 166 159 176 136 147 3.38
70 233 200 167 178 4.95
95 284 237 204 212 6.86
120 330 269 236 241 8.66
150 380 305 273 274 10.64
185 436 343 313 308 13.37
240 515 396 369 355 17.54

* The same for four-lead with zero lead of smaller cut. For determination of four current loads with cable leads of equal cuts in four-wire nets under the load in all leads in normal mode data about load should be multiplied by 0.93.

Cable leads amount and nominal cut, mm² Nominal external diameter, mm 1 km cable bulk, kg
Cable marks with sector cable lead
3×70 32.8 1578
3×95 36.9 1976
3×120 40.1 2304
3×150 42.7 2683
3×185 46.8 3190
3×240 52.0 3911
3×70+1×25 37.7 1844
3×70+1×35 37.7 1877
3×95+1×35 41.6 2249
3×95+1×50 41.6 2303
3×120+1×35 43.8 2549
3×120+1×70 45.9 2761
3×150+1×50 47.8 3054
3×150+1×70 47.8 3122
3×185+1×50 52.2 3540
3×185+1×95 52.7 3720
3×240+1×70 57.9 4409
3×240+1×120 57.9 4586
4×70 39.8 2064
4×95 41.6 2468
4×120 45.4 2935
4×150 49.2 3442
4×185 53.2 4037
4×240 59.4 5025
Cable marks with round cable lead
1×25
1×35
1×50
2×25 25.2 779
2×35 27.5 906
2×50 31.1 1108
3×25 26.5 928
3×35 29.0 1094
3×50 32.8 1358
3×25+1×16 28.0 1033
3×35+1×16 29.8 1183
3×50+1×25 34.7 1521
4×25 28.8 1102
4×35 31.6 1310
4×50 36.2 1676